18 — Calculators
Calculate starting current and voltage dip
The starting current is on the nameplate and quickly worked out. The interesting question is the second one: what does that current do to the voltage in the network? If the lights flicker and the controller reboots whenever the big pump starts, the answer is here.
Result
- Starting current
- —A
- Voltage dip at startRelative to the system voltage at the connection point.
- —%
- Starting apparent power
- —kVA
- Voltage remaining during start
- —V
- Remaining starting torqueTorque falls with the square of the voltage — which is why a dip can prevent the start altogether.
- —%
Please fill all fields with valid numbers.
- Opens the print dialog. Choose “Save as PDF” as the destination.
- Opens your email program with the values from this calculation. Nothing is sent to us until you send it yourself.
A guide, not a design to standard. We give no warranty for the correctness of the results, the applicable standards and case-by-case verification govern.
Worked example
The default case the calculator starts with, worked through once. Change the values above and it recalculates immediately.
Inputs
- Rated motor current
- 55 A
- Starting current ratio I_A / I_N
- 7
- System voltage
- 400 V
- Network impedance at the connection point
- 0.02 Ω
- Power factor at start
- 0.3
Result
- Starting current
- 385 A
- Voltage dip at start
- 3.18 %
- Starting apparent power
- 267 kVA
- Voltage remaining during start
- 387 V
- Remaining starting torque
- 93.7 %
Formula
- I_A = I_N · (I_A / I_N)
- ΔU/U ≈ √3 · I_A · Z_network · sin φ_A / U
- S_A = √3 · U · I_A
- M_A(U) / M_A(U_N) = (U / U_N)²
Assumptions and standards
- The starting current is strongly inductive. What drives the voltage dip is therefore mainly the reactive component, and that is what is used.
- The network impedance is entered here. It covers everything from the supply up to the motor connection point.
- The calculation describes the instant after switching on, with the rotor at standstill. As speed rises the current falls.
- An estimate. The actual current curve against speed depends on the motor type and is not linear.
Frequently asked
What voltage dip is still acceptable?
It depends on what else is on the same network. Lighting shows a few percent as visible flicker. Contactor coils typically drop out below seventy to eighty percent of nominal voltage — then the installation switches itself off at every start. Network operators set their own limits at the point of supply.
Why is starting torque so sensitive?
Because it goes with the square of the voltage. Ten percent less voltage means nineteen percent less torque. If the voltage dips badly, the torque may no longer overcome the load torque — the motor stalls and keeps drawing starting current until the protection operates.
What helps against too large a dip?
Either reduce the impedance — larger cross-section, shorter feeder, stronger transformer — or limit the starting current: star-delta, soft starter or variable frequency drive. Which route is right is decided by the load torque that still has to be overcome.
Calculating is the easy part.
A formula gives you a number. Designing a plant also demands installation method, grouping, discrimination, the standards in force and a look at the installed base. That is what we take on.
More tools
- 01Cable cross-section
- 02Voltage drop
- 03Cable resistance
- 04Cable losses
- 05Maximum cable length
- 06Current-carrying capacity
- 07Parallel cables
- 08Conductor temperature
- 09Cable capacitance
- 10Short-circuit current
- 11Cable impedance
- 12Network impedance
- 13Short-circuit current at the far end
- 14Thermal short-circuit withstand
- 15Length and disconnection
- 16Motor current
- 17Torque
- 19Star-delta starting
- 20Soft starting
- 21Motor efficiency
- 22Speed control instead of throttling
- 23Speed and slip
- 24Setting the motor protection
- 25Single-phase motor
- 26Motor feeder
- 27Required motor rating
- 28PFD and SIL
- 29PFH and SIL
- 30Protective conductor size
- 31Earth rod
- 32Touch voltage
- 33Residual current protection
- 34Check discrimination
- 35Connecting a surge arrester
- 36Enclosure cooling
- 37Reference designation
- 38Reactive power compensation
Contact
Tell us what it is about.
A phone call or three lines is enough. From the very start you talk to the people who will later work on your project, not to a distribution list.
Direct
- Phone+49 (0) 5247 4070-66
- Emailinfo@fisekon.com
- AvailabilityMon – Fri, 8:00 – 17:00 CET
Locations
33428 Marienfeld (Harsewinkel)Gütersloh officeWagenfeldstr. 2
33332 Gütersloh
Or write to us
We usually reply within one working day.
