Calculators
Calculate cable cross-section
Two conditions determine the cross-section of a cable. It has to carry the current thermally, and the voltage drop over the length has to stay within the permitted range. The calculator checks both and returns the larger cross-section. On long runs that is usually the one by voltage drop, on short runs almost always the one by heating.
Result
- Required cross-sectionLarger of voltage drop and current-carrying capacity
- —mm²
- Governing condition
- —
- Cross-section by current-carrying capacityIEC 60364-5-52, Annex B
- —mm²
- Cross-section by voltage dropSeries to IEC 60228
- —mm²
- Current-carrying capacity I_zAt least the protective device rating
- —A
- Calculated by voltage drop
- —mm²
- Permissible voltage drop
- —V
- Actual voltage drop at the selected cross-section
- —%
Please fill all fields with valid numbers.
A guide, not a design to standard. We give no warranty for the correctness of the results. The applicable standards and case-by-case verification govern.
The grey values are an example. Simply enter your own.
Matching services
Calculating is the easy part.
A formula gives you a number. Designing a plant also demands installation method, grouping, discrimination, the standards in force and a look at the installed base. That is what we take on.
Method and questions
Cable cross-section
Required cross-section from voltage drop and current-carrying capacity.
Discuss a projectWorked example
The default case the calculator starts with, worked through once. Change the values above and it recalculates immediately.
Inputs
- System
- Three-phase (3~)
- Operating current
- 32 A
- One-way cable length
- 45 m
- Nominal voltage
- 400 V
- Permissible voltage drop
- 3 %
- Power factor cos φ
- 0.9
- Conductor material
- Copper (κ = 56 m/Ω·mm²)
- Installation method
- C · Multi-core cable directly on a wall
- Ambient temperature
- 30 °C
- Circuits installed together
- this cable only
Result
- Required cross-section
- 4 mm²
- Governing condition
- Both conditions lead to the same cross-section.
- Cross-section by current-carrying capacity
- 4 mm²
- Cross-section by voltage drop
- 4 mm²
- Current-carrying capacity I_z
- 32 A
- Calculated by voltage drop
- 3.34 mm²
- Permissible voltage drop
- 12 V
- Actual voltage drop at the selected cross-section
- 2.51 %
Formula and standards
Formula
- Three-phase A = (√3 · L · I · cos φ) / (κ · Δu)
- Single-phase A = (2 · L · I · cos φ) / (κ · Δu)
- DC A = (2 · L · I) / (κ · Δu)
- Δu = U · Δu% / 100
- A_req = max(A_voltage drop, A_current capacity)
Assumptions and standards
- κ = 56 m/(Ω·mm²) for copper, 35 m/(Ω·mm²) for aluminium at 20 °C.
- Calculated with the resistive component only. Inductive reactance is not included. For large cross-sections from about 95 mm² and long runs the result is therefore slightly optimistic.
- Current-carrying capacity to IEC 60364-5-52, Annex B, for PVC-insulated copper cables, 70 °C conductor temperature, reference 30 °C air. Corrected with the ambient temperature factor and the grouping factor for bunched circuits.
- Three conductors are loaded in three-phase systems, two in single-phase and DC. Harmonic currents in the neutral are not considered.
- The capacity of the result must at least cover the rated current of the protective device (I_B ≤ I_n ≤ I_z). No capacity values are stored for aluminium.
- Standard cross-sections to IEC 60228.
What voltage drop is permissible?
In Germany, 3 % for lighting and 5 % for other loads is customary for consumer installations, measured from the point of supply. Industrial plants often apply stricter internal limits, the operator’s specification always governs.
Why is the one-way length used?
The return path is already in the factor, which is 2 for single-phase and DC and √3 for three-phase. So enter the one-way distance from supply to load.
Does this replace design to standard?
No. The calculator combines voltage drop and current-carrying capacity. A complete design also covers coordination with the protective device, short-circuit withstand and the disconnection condition.
More calculators on this topic
Contact
Planning a system right now?
We take on the electrical design, from sizing and EPLAN schematics to the finished documentation. A call or three lines are enough.
Direct
- Phone+49 (0) 5247 4070-66
- Emailinfo@fisekon.com
- AvailabilityMon to Fri, 8 am to 5 pm CET
Or write to us
We usually reply within one working day.


