FISEKON GmbH · Fischer Elektrokonstruktion

Calculators

Calculate cable cross-section

Two conditions determine the cross-section of a cable. It has to carry the current thermally, and the voltage drop over the length has to stay within the permitted range. The calculator checks both and returns the larger cross-section. On long runs that is usually the one by voltage drop, on short runs almost always the one by heating.

Input

Typically 3 % for lighting and 5 % for other loads.

For PVC-insulated copper cables, 70 °C. With XLPE insulation the result is on the safe side. Rubber cables such as H07RN-F are not covered.

The air at the cable, not in the room. Inside an enclosure or at the machine it is often well above 30 °C.

Loaded circuits laid together in trunking, in a bundle or on a wall. This cable counts.

Result

Required cross-sectionLarger of voltage drop and current-carrying capacity
—mm²
Governing condition
—
Cross-section by current-carrying capacityIEC 60364-5-52, Annex B
—mm²
Cross-section by voltage dropSeries to IEC 60228
—mm²
Current-carrying capacity I_zAt least the protective device rating
—A
Calculated by voltage drop
—mm²
Permissible voltage drop
—V
Actual voltage drop at the selected cross-section
—%

A guide, not a design to standard. We give no warranty for the correctness of the results. The applicable standards and case-by-case verification govern.

Result as PDF

Where should we send the PDF?

You receive inputs, result and formula as a PDF by email, to file or pass on.

The grey values are an example. Simply enter your own.

Matching services

Calculating is the easy part.

A formula gives you a number. Designing a plant also demands installation method, grouping, discrimination, the standards in force and a look at the installed base. That is what we take on.

Discuss a project

Method and questions

Cable cross-section

Required cross-section from voltage drop and current-carrying capacity.

Discuss a project
Worked example

The default case the calculator starts with, worked through once. Change the values above and it recalculates immediately.

Inputs

System
Three-phase (3~)
Operating current
32 A
One-way cable length
45 m
Nominal voltage
400 V
Permissible voltage drop
3 %
Power factor cos φ
0.9
Conductor material
Copper (κ = 56 m/Ω·mm²)
Installation method
C · Multi-core cable directly on a wall
Ambient temperature
30 °C
Circuits installed together
this cable only

Result

Required cross-section
4 mm²
Governing condition
Both conditions lead to the same cross-section.
Cross-section by current-carrying capacity
4 mm²
Cross-section by voltage drop
4 mm²
Current-carrying capacity I_z
32 A
Calculated by voltage drop
3.34 mm²
Permissible voltage drop
12 V
Actual voltage drop at the selected cross-section
2.51 %
Formula and standards

Formula

  • Three-phase A = (√3 · L · I · cos φ) / (κ · Δu)
  • Single-phase A = (2 · L · I · cos φ) / (κ · Δu)
  • DC A = (2 · L · I) / (κ · Δu)
  • Δu = U · Δu% / 100
  • A_req = max(A_voltage drop, A_current capacity)

Assumptions and standards

  • κ = 56 m/(Ω·mm²) for copper, 35 m/(Ω·mm²) for aluminium at 20 °C.
  • Calculated with the resistive component only. Inductive reactance is not included. For large cross-sections from about 95 mm² and long runs the result is therefore slightly optimistic.
  • Current-carrying capacity to IEC 60364-5-52, Annex B, for PVC-insulated copper cables, 70 °C conductor temperature, reference 30 °C air. Corrected with the ambient temperature factor and the grouping factor for bunched circuits.
  • Three conductors are loaded in three-phase systems, two in single-phase and DC. Harmonic currents in the neutral are not considered.
  • The capacity of the result must at least cover the rated current of the protective device (I_B ≤ I_n ≤ I_z). No capacity values are stored for aluminium.
  • Standard cross-sections to IEC 60228.
What voltage drop is permissible?

In Germany, 3 % for lighting and 5 % for other loads is customary for consumer installations, measured from the point of supply. Industrial plants often apply stricter internal limits, the operator’s specification always governs.

Why is the one-way length used?

The return path is already in the factor, which is 2 for single-phase and DC and √3 for three-phase. So enter the one-way distance from supply to load.

Does this replace design to standard?

No. The calculator combines voltage drop and current-carrying capacity. A complete design also covers coordination with the protective device, short-circuit withstand and the disconnection condition.

Contact

Planning a system right now?

We take on the electrical design, from sizing and EPLAN schematics to the finished documentation. A call or three lines are enough.

Direct

Or write to us

We usually reply within one working day.

We only use your details to answer your enquiry. More in our privacy policy.

Go to the contact form

Olaf Kreith

Your contactOlaf KreithHead of Sales

Quick question

Do you need help or have any questions?

Tell us briefly what it is about. We usually reply within one working day.