FISEKON GmbH · Fischer Elektrokonstruktion

Calculators

Size a motor feeder

Motor cables are usually sized for the operating current. Then people wonder why the motor starts sluggishly on a long run. The starting current drops across the same cable, and a multiple of the current means a multiple of the voltage drop.

Input

For the motor feeder alone, not for the whole installation.

For PVC-insulated copper cables, 70 °C. With XLPE insulation the result is on the safe side. Rubber cables such as H07RN-F are not covered.

The air at the cable, not in the room. Inside an enclosure or at the machine it is often well above 30 °C.

Loaded circuits laid together in trunking, in a bundle or on a wall. This cable counts.

Result

Required cross-section, standard sizeLarger of voltage drop and current-carrying capacity
—mm²
Governing condition
—
Cross-section by voltage drop
—mm²
Rated motor current
—A
Calculated by voltage drop
—mm²
Voltage drop in operation at this size
—%
Voltage drop on the cable at startAdds to the dip in the network.
—%

A guide, not a design to standard. We give no warranty for the correctness of the results. The applicable standards and case-by-case verification govern.

Result as PDF

Where should we send the PDF?

You receive inputs, result and formula as a PDF by email, to file or pass on.

The grey values are an example. Simply enter your own.

Matching services

Calculating is the easy part.

A formula gives you a number. Designing a plant also demands installation method, grouping, discrimination, the standards in force and a look at the installed base. That is what we take on.

Discuss a project

Method and questions

Motor feeder

Current and cross-section of the motor cable, including the voltage drop at start.

Discuss a project
Worked example

The default case the calculator starts with, worked through once. Change the values above and it recalculates immediately.

Inputs

Rated motor power
30 kW
System voltage
400 V
Efficiency
92 %
Power factor cos φ
0.86
Length of the feeder
80 m
Permissible voltage drop in operation
3 %
Starting current ratio I_A / I_N
7
Conductor material
Copper (κ = 56 m/Ω·mm²)
Installation method
C · Multi-core cable directly on a wall
Ambient temperature
30 °C
Circuits installed together
this cable only

Result

Required cross-section, standard size
10 mm²
Governing condition
Both conditions lead to the same cross-section.
Cross-section by voltage drop
10 mm²
Rated motor current
54.7 A
Calculated by voltage drop
9.7 mm²
Voltage drop in operation at this size
2.91 %
Voltage drop on the cable at start
7.11 %
Formula and standards

Formula

  • P_in = P_out / η
  • I_N = P_in / (√3 · U · cos φ)
  • A = (√3 · L · I_N · cos φ) / (κ · Δu)
  • At start Δu_A ≈ (√3 · L · I_A · cos φ_A) / (κ · A)

Assumptions and standards

  • The cross-section is the larger of operating voltage drop and current-carrying capacity to IEC 60364-5-52, Annex B (PVC-insulated copper cable, three loaded conductors). Short-circuit protection and the disconnection condition are separate proofs.
  • For starting, a power factor of 0.3 is used, because at start the motor is strongly inductive.
  • For inverter-fed motors, additional requirements on screening and length apply that are not covered here.
What voltage drop is still acceptable at start?

It adds to the dip in the supplying network. Together they determine what reaches the motor, and starting torque falls with the square of that. If less than eighty percent of nominal voltage remains, starting heavy loads becomes unreliable.

Why is the operating current not enough for sizing?

It is enough for heating, not for starting behaviour. A cable with three percent drop in operation reaches a multiple of that at seven times the current. And that is exactly the moment the motor needs the voltage most.

Does this apply with a variable frequency drive?

The starting part does not. A drive limits the current and ramps up the frequency, so there is no inrush. Other topics arrive instead, such as screening, leakage currents and the permissible cable length per the drive manufacturer.

Contact

Planning a system right now?

We take on the electrical design, from sizing and EPLAN schematics to the finished documentation. A call or three lines are enough.

Direct

Or write to us

We usually reply within one working day.

We only use your details to answer your enquiry. More in our privacy policy.

Go to the contact form

Olaf Kreith

Your contactOlaf KreithHead of Sales

Quick question

Do you need help or have any questions?

Tell us briefly what it is about. We usually reply within one working day.