26 — Calculators
Size a motor feeder
Motor cables are usually sized for the operating current — and then people wonder why the motor starts sluggishly on a long run. The starting current drops across the same cable, and a multiple of the current means a multiple of the voltage drop.
Result
- Required cross-section, standard size
- —mm²
- Rated motor current
- —A
- Calculated cross-section
- —mm²
- Voltage drop in operation at this size
- —%
- Voltage drop on the cable at startAdds to the dip in the network.
- —%
Please fill all fields with valid numbers.
- Opens the print dialog. Choose “Save as PDF” as the destination.
- Opens your email program with the values from this calculation. Nothing is sent to us until you send it yourself.
A guide, not a design to standard. We give no warranty for the correctness of the results, the applicable standards and case-by-case verification govern.
Worked example
The default case the calculator starts with, worked through once. Change the values above and it recalculates immediately.
Inputs
- Rated motor power
- 30 kW
- System voltage
- 400 V
- Efficiency
- 92 %
- Power factor cos φ
- 0.86
- Length of the feeder
- 80 m
- Permissible voltage drop in operation
- 3 %
- Starting current ratio I_A / I_N
- 7
- Conductor material
- Copper (κ = 56 m/Ω·mm²)
Result
- Required cross-section, standard size
- 10 mm²
- Rated motor current
- 54.7 A
- Calculated cross-section
- 9.7 mm²
- Voltage drop in operation at this size
- 2.91 %
- Voltage drop on the cable at start
- 7.11 %
Formula
- P_in = P_out / η
- I_N = P_in / (√3 · U · cos φ)
- A = (√3 · L · I_N · cos φ) / (κ · Δu)
- Starting: Δu_A ≈ (√3 · L · I_A · cos φ_A) / (κ · A)
Assumptions and standards
- The cross-section here follows from the operating voltage drop alone. Current-carrying capacity, short-circuit protection and the disconnection condition are separate proofs.
- For starting, a power factor of 0.3 is used — at start the motor is strongly inductive.
- For inverter-fed motors, additional requirements on screening and length apply that are not covered here.
Frequently asked
What voltage drop is still acceptable at start?
It adds to the dip in the supplying network. Together they determine what reaches the motor — and starting torque falls with the square of that. If less than eighty percent of nominal voltage remains, starting heavy loads becomes unreliable.
Why is the operating current not enough for sizing?
It is enough for heating, not for starting behaviour. A cable with three percent drop in operation reaches a multiple of that at seven times the current — and that is exactly the moment the motor needs the voltage most.
Does this apply with a variable frequency drive?
The starting part does not: a drive limits the current and ramps up the frequency, so there is no inrush. Other topics arrive instead — screening, leakage currents, permissible cable length per the drive manufacturer.
Calculating is the easy part.
A formula gives you a number. Designing a plant also demands installation method, grouping, discrimination, the standards in force and a look at the installed base. That is what we take on.
More tools
- 01Cable cross-section
- 02Voltage drop
- 03Cable resistance
- 04Cable losses
- 05Maximum cable length
- 06Current-carrying capacity
- 07Parallel cables
- 08Conductor temperature
- 09Cable capacitance
- 10Short-circuit current
- 11Cable impedance
- 12Network impedance
- 13Short-circuit current at the far end
- 14Thermal short-circuit withstand
- 15Length and disconnection
- 16Motor current
- 17Torque
- 18Starting current
- 19Star-delta starting
- 20Soft starting
- 21Motor efficiency
- 22Speed control instead of throttling
- 23Speed and slip
- 24Setting the motor protection
- 25Single-phase motor
- 27Required motor rating
- 28PFD and SIL
- 29PFH and SIL
- 30Protective conductor size
- 31Earth rod
- 32Touch voltage
- 33Residual current protection
- 34Check discrimination
- 35Connecting a surge arrester
- 36Enclosure cooling
- 37Reference designation
- 38Reactive power compensation
Contact
Tell us what it is about.
A phone call or three lines is enough. From the very start you talk to the people who will later work on your project, not to a distribution list.
Direct
- Phone+49 (0) 5247 4070-66
- Emailinfo@fisekon.com
- AvailabilityMon – Fri, 8:00 – 17:00 CET
Locations
33428 Marienfeld (Harsewinkel)Gütersloh officeWagenfeldstr. 2
33332 Gütersloh
Or write to us
We usually reply within one working day.
