Calculators
Calculate maximum cable length
This question usually comes from site, not from the desk. The cross-section is fixed, and the route turns out longer than planned. Will it still do? This calculation inverts the voltage-drop formula and answers in metres.
Result
- Maximum cable length
- —m
- Voltage drop at that length
- —V
- Length at the next size upWhat one size more copper buys in distance.
- —m
- Does the cross-section carry the current?
- —
Please fill all fields with valid numbers.
A guide, not a design to standard. We give no warranty for the correctness of the results. The applicable standards and case-by-case verification govern.
The grey values are an example. Simply enter your own.
Matching services
Calculating is the easy part.
A formula gives you a number. Designing a plant also demands installation method, grouping, discrimination, the standards in force and a look at the installed base. That is what we take on.
Method and questions
Maximum cable length
How far a cross-section reaches before the voltage drop exceeds the limit.
Discuss a projectWorked example
The default case the calculator starts with, worked through once. Change the values above and it recalculates immediately.
Inputs
- System
- Three-phase (3~)
- Operating current
- 32 A
- Conductor cross-section
- 6 mm²
- Nominal voltage
- 400 V
- Permissible voltage drop
- 3 %
- Power factor cos φ
- 0.9
- Conductor material
- Copper (κ = 56 m/Ω·mm²)
Result
- Maximum cable length
- 80.8 m
- Voltage drop at that length
- 12 V
- Length at the next size up
- 135 m
- Does the cross-section carry the current?
- In free air, yes. Installation method, grouping and ambient temperature remain to be checked to IEC 60364-5-52. The cable cross-section calculator does that.
Formula and standards
Formula
- Three-phase L_max = (Δu · κ · A) / (√3 · I · cos φ)
- Single-phase L_max = (Δu · κ · A) / (2 · I · cos φ)
- DC L_max = (Δu · κ · A) / (2 · I)
- Δu = U · Δu% / 100
Assumptions and standards
- κ = 56 m/(Ω·mm²) for copper, 35 m/(Ω·mm²) for aluminium at 20 °C.
- Voltage drop is the only criterion here. Current-carrying capacity, short-circuit protection and the disconnection condition limit the length independently.
- At operating temperature the resistance rises. The length actually permissible is then roughly one sixth below the calculated value.
Does this settle the length?
No. As length increases, the short-circuit current at the far end falls. At some point it is no longer enough to trip the protective device within the required time. Then the disconnection condition, not the voltage drop, is the tighter limit.
Which permissible voltage drop should I use?
The common values are 3 percent for lighting and 5 percent for other loads. What matters is the point the calculation starts from and how much has already been used up. Downstream of a sub-distribution board, less is left for the final circuits.
Why show the next size up?
Because in practice that is the real question. Not how far you get, but what it costs to get further. Length grows in proportion to cross-section.
More calculators on this topic
Contact
Planning a system right now?
We take on the electrical design, from sizing and EPLAN schematics to the finished documentation. A call or three lines are enough.
Direct
- Phone+49 (0) 5247 4070-66
- Emailinfo@fisekon.com
- AvailabilityMon to Fri, 8 am to 5 pm CET
Or write to us
We usually reply within one working day.

