Calculators
Setting a motor overload relay
An overload relay in the delta branch does not see the line current but the winding current, which is smaller by a factor of root three. Set the nameplate value there and the motor is protected forty percent too high. It is one of the most common mistakes in star-delta circuits.
Result
- Value to set
- —A
- Assessment
- —
- Estimated tripping time at starting currentAn approximation from the trip class. The characteristic in the data sheet governs.
- —s
- Deviation of the setting from the target
- —%
Please fill all fields with valid numbers.
A guide, not a design to standard. We give no warranty for the correctness of the results. The applicable standards and case-by-case verification govern.
The grey values are an example. Simply enter your own.
Matching services
Calculating is the easy part.
A formula gives you a number. Designing a plant also demands installation method, grouping, discrimination, the standards in force and a look at the installed base. That is what we take on.
Method and questions
Setting the motor protection
The correct setting, and the star-delta trap.
Discuss a projectWorked example
The default case the calculator starts with, worked through once. Change the values above and it recalculates immediately.
Inputs
- Rated motor current
- 55 A
- Location of the overload relay
- In the line feeder (direct on line)
- Value set on the relay
- 55 A
- Tripping time of the trip class
- 10 s
- Starting current
- 385 A
- Duration of the start
- 4 s
Result
- Value to set
- 55 A
- Assessment
- The setting matches the calculated target.
- Estimated tripping time at starting current
- 10.6 s
- Deviation of the setting from the target
- 0 %
Formula and standards
Formula
- Direct on line: I_e = I_N
- In the delta branch: I_e = I_N / √3
- Approximate tripping time t ≈ t_class · (7.2 / (I / I_e))²
Assumptions and standards
- The setting follows the rated motor current for the actual duty type. Intermittent duty or different cooling call for different values.
- The tripping time is an approximation from the thermal model and only serves to estimate whether the start gets through. The characteristic in the device data sheet governs.
- An overload relay protects against overload, not against short circuit. Short-circuit protection is a separate device and a separate design.
Why root three?
Because in delta connection the line current divides between three windings, and each winding carries only the line current divided by root three. With the relay in that branch, it measures this smaller current. At 55 A motor current that is around 32 A.
What if the relay trips during starting?
Then the trip class does not match the starting time. A higher class allows more time, but the motor has to withstand it thermally as well. With heavy starts, checking that motor and relay match is not a formality.
Is a motor protection circuit breaker enough on its own?
It combines overload and short-circuit release in one device and suffices for many applications. Where short-circuit currents at the point of installation are high, its breaking capacity has to match. Otherwise a fuse upstream is needed.
More calculators on this topic
Contact
Planning a system right now?
We take on the electrical design, from sizing and EPLAN schematics to the finished documentation. A call or three lines are enough.
Direct
- Phone+49 (0) 5247 4070-66
- Emailinfo@fisekon.com
- AvailabilityMon to Fri, 8 am to 5 pm CET
Or write to us
We usually reply within one working day.

