35 — Calculators
Lead length for surge protective devices
An arrester with a good protection level is worthless if it hangs on a metre of wire. Under an impulse the current rises within microseconds — and across an inductance that produces a voltage which can double the protection level. That is the reason for the rule to keep the leads short.
Result
- Effective protection level at the equipmentProtection level plus the voltage across the connecting leads.
- —kV
- Assessment
- —
- Voltage across the connecting leads
- —kV
- Share of the leads in the protection levelThis is where it is decided whether the installation defeats the SPD.
- —%
- Greatest lead length for this equipment
- —m
Please fill all fields with valid numbers.
- Opens the print dialog. Choose “Save as PDF” as the destination.
- Opens your email program with the values from this calculation. Nothing is sent to us until you send it yourself.
A guide, not a design to standard. We give no warranty for the correctness of the results, the applicable standards and case-by-case verification govern.
Worked example
The default case the calculator starts with, worked through once. Change the values above and it recalculates immediately.
Inputs
- Voltage protection level U_p of the SPD
- 1.5 kV
- Total length of the connecting leads
- 1 m
- Inductance per metre
- 1 µH/m
- Impulse current through the SPD
- 5 kA
- Front time of the impulse current
- 8 µs
- Impulse withstand voltage U_w of the equipment
- 2.5 kV
Result
- Effective protection level at the equipment
- 2.13 kV
- Assessment
- The effective protection level is below it, but without much margin.
- Voltage across the connecting leads
- 0.625 kV
- Share of the leads in the protection level
- 29.4 %
- Greatest lead length for this equipment
- 1.6 m
Formula
- u = L · di/dt
- L = L′ · l
- di/dt ≈ I / t_r
- U_effective = U_p + u
- l_max = (U_w − U_p) / (u per metre)
Assumptions and standards
- The inductance per metre is an empirical value for straight single conductors and is entered here. Loops and wide conductor spacing raise it considerably.
- The length is the sum of both legs — the lead to the arrester and the connection to the earthing bar.
- A linear current rise is assumed. The actual impulse waveform rises more steeply at first; the calculated value is a lower estimate.
- Contributions from coupling with neighbouring cables and from the distance between arrester and equipment are not included.
Frequently asked
Where does the half-metre rule come from?
From exactly this calculation. At usual impulse currents and rise times the voltage across the leads is of the order of a kilovolt per metre. Half a metre of total length keeps that share small enough for the arrester protection level to retain its meaning.
What if I cannot get below that length?
V-shaped wiring helps: incoming and outgoing conductors are taken directly to the arrester terminals, so the arrester lies in the current path rather than on a stub. That largely removes the additional voltage.
Why does the front time matter so much?
Because the voltage depends on the rate of rise, not on the current alone. The same peak value in half the time gives twice the voltage. That is why lightning impulses with a steep front are more critical for lead length than higher-energy but slower waveforms.
Calculating is the easy part.
A formula gives you a number. Designing a plant also demands installation method, grouping, discrimination, the standards in force and a look at the installed base. That is what we take on.
More tools
- 01Cable cross-section
- 02Voltage drop
- 03Cable resistance
- 04Cable losses
- 05Maximum cable length
- 06Current-carrying capacity
- 07Parallel cables
- 08Conductor temperature
- 09Cable capacitance
- 10Short-circuit current
- 11Cable impedance
- 12Network impedance
- 13Short-circuit current at the far end
- 14Thermal short-circuit withstand
- 15Length and disconnection
- 16Motor current
- 17Torque
- 18Starting current
- 19Star-delta starting
- 20Soft starting
- 21Motor efficiency
- 22Speed control instead of throttling
- 23Speed and slip
- 24Setting the motor protection
- 25Single-phase motor
- 26Motor feeder
- 27Required motor rating
- 28PFD and SIL
- 29PFH and SIL
- 30Protective conductor size
- 31Earth rod
- 32Touch voltage
- 33Residual current protection
- 34Check discrimination
- 36Enclosure cooling
- 37Reference designation
- 38Reactive power compensation
Contact
Tell us what it is about.
A phone call or three lines is enough. From the very start you talk to the people who will later work on your project, not to a distribution list.
Direct
- Phone+49 (0) 5247 4070-66
- Emailinfo@fisekon.com
- AvailabilityMon – Fri, 8:00 – 17:00 CET
Locations
33428 Marienfeld (Harsewinkel)Gütersloh officeWagenfeldstr. 2
33332 Gütersloh
Or write to us
We usually reply within one working day.
