31 — Calculators
Earth resistance of a vertical rod electrode
Earth resistance depends almost entirely on the soil and the length of the electrode — diameter enters only logarithmically. Measure too high a value and a thicker rod barely helps, whereas a longer one does.
Result
- Earth resistance of the arrangement
- —Ω
- Earth resistance of a single electrode
- —Ω
- At double electrode lengthLength works harder than diameter — go deeper, not thicker.
- —Ω
- Largest permissible earth resistanceFrom the condition R_A · I_Δn ≤ 50 V.
- —Ω
- Is the earthing sufficient for this device?
- —
Please fill all fields with valid numbers.
- Opens the print dialog. Choose “Save as PDF” as the destination.
- Opens your email program with the values from this calculation. Nothing is sent to us until you send it yourself.
A guide, not a design to standard. We give no warranty for the correctness of the results, the applicable standards and case-by-case verification govern.
Worked example
The default case the calculator starts with, worked through once. Change the values above and it recalculates immediately.
Inputs
- Soil resistivity
- 150 Ω·m
- Length of the electrode
- 9 m
- Diameter of the electrode
- 20 mm
- Number of parallel electrodes
- 1
- Utilisation factor for several electrodes
- 0.8
- Rated residual current of the protective device
- 300 mA
Result
- Earth resistance of the arrangement
- 19.9 Ω
- Earth resistance of a single electrode
- 19.9 Ω
- At double electrode length
- 10.9 Ω
- Largest permissible earth resistance
- 167 Ω
- Is the earthing sufficient for this device?
- Yes, with margin. The earth resistance is well below the permissible value.
Formula
- R = ρ / (2π · L) · ln(4L / d)
- For n electrodes: R_total = R / (n · utilisation factor)
- Condition for a residual current device: R_A · I_Δn ≤ 50 V
Assumptions and standards
- The formula applies to a rod driven vertically into uniform soil. Layered soil, rock or groundwater change the result considerably.
- Soil resistivity has to be measured. It varies strongly with the season — in summer and under frost it is markedly higher than in a wet spring.
- The utilisation factor represents the mutual influence of several electrodes and is entered here. At spacing below the electrode length it drops sharply.
- Strip and ring electrodes follow a different formula. This calculator covers the rod electrode only.
- The utilisation factor takes effect from two electrodes upwards. For a single electrode the calculated value stays unchanged.
Frequently asked
Why does a longer rod help more than a thicker one?
Because length sits in the denominator while diameter appears only inside the logarithm. Doubling the length nearly halves the resistance. Doubling the diameter gains only a few percent depending on the ratio — and costs considerably more material.
Why do two electrodes not behave like two parallel resistors?
Because they share the same volume of earth. Placed close together their fields overlap and each performs worse than it would alone. Hence the utilisation factor — and hence the rule to keep at least the electrode length as spacing.
How does this relate to the residual current device?
In a TT system the fault current returns through earth. The touch voltage follows from earth resistance times operating current and has to stay below the permitted limit. That is why the largest permissible earth resistance is shown here alongside.
Calculating is the easy part.
A formula gives you a number. Designing a plant also demands installation method, grouping, discrimination, the standards in force and a look at the installed base. That is what we take on.
More tools
- 01Cable cross-section
- 02Voltage drop
- 03Cable resistance
- 04Cable losses
- 05Maximum cable length
- 06Current-carrying capacity
- 07Parallel cables
- 08Conductor temperature
- 09Cable capacitance
- 10Short-circuit current
- 11Cable impedance
- 12Network impedance
- 13Short-circuit current at the far end
- 14Thermal short-circuit withstand
- 15Length and disconnection
- 16Motor current
- 17Torque
- 18Starting current
- 19Star-delta starting
- 20Soft starting
- 21Motor efficiency
- 22Speed control instead of throttling
- 23Speed and slip
- 24Setting the motor protection
- 25Single-phase motor
- 26Motor feeder
- 27Required motor rating
- 28PFD and SIL
- 29PFH and SIL
- 30Protective conductor size
- 32Touch voltage
- 33Residual current protection
- 34Check discrimination
- 35Connecting a surge arrester
- 36Enclosure cooling
- 37Reference designation
- 38Reactive power compensation
Contact
Tell us what it is about.
A phone call or three lines is enough. From the very start you talk to the people who will later work on your project, not to a distribution list.
Direct
- Phone+49 (0) 5247 4070-66
- Emailinfo@fisekon.com
- AvailabilityMon – Fri, 8:00 – 17:00 CET
Locations
33428 Marienfeld (Harsewinkel)Gütersloh officeWagenfeldstr. 2
33332 Gütersloh
Or write to us
We usually reply within one working day.
