30 — Calculators
Determine the protective conductor cross-section
There are two routes to a protective conductor: calculate or allocate. Allocation by line conductor size is quick but not always the safe side — with high short-circuit currents and slow protective devices the thermal proof demands more. This calculator shows both and takes the larger.
Result
- Governing cross-sectionThe larger of the two routes below.
- —mm²
- Calculated from heatingThe thermal proof: A = I · √t / k.
- —mm²
- From the simplified allocationUp to 16 mm² equal to the line conductor, up to 35 mm² sixteen, above that half.
- —mm²
- Next standard cross-section
- —mm²
Please fill all fields with valid numbers.
- Opens the print dialog. Choose “Save as PDF” as the destination.
- Opens your email program with the values from this calculation. Nothing is sent to us until you send it yourself.
A guide, not a design to standard. We give no warranty for the correctness of the results, the applicable standards and case-by-case verification govern.
Worked example
The default case the calculator starts with, worked through once. Change the values above and it recalculates immediately.
Inputs
- Line conductor cross-section
- 35 mm²
- Fault current through the protective conductor
- 6 kA
- Disconnection time
- 0.2 s
- Material factor k
- 143
Result
- Governing cross-section
- 18.8 mm²
- Calculated from heating
- 18.8 mm²
- From the simplified allocation
- 16 mm²
- Next standard cross-section
- 25 mm²
Formula
- Thermal: A = I · √t / k
- Simplified: A ≤ 16 mm² → A_PE = A
- 16 < A ≤ 35 mm² → A_PE = 16 mm²
- A > 35 mm² → A_PE = A / 2
Assumptions and standards
- The material factor k applies to the protective conductor and differs from that for the line conductor — it depends on material, insulation and whether the protective conductor is part of the cable or laid separately. It is entered, not looked up.
- The simplified allocation assumes protective and line conductors are of the same material. With different materials a conversion is required.
- Protective conductors that are not part of a cable are subject to additional minimum sizes against mechanical damage.
Frequently asked
Why is the simplified allocation not always enough?
Because it does not know the fault current or the disconnection time. On short feeders with high short-circuit current and a slow protective device, heating can demand more than the allocation gives. Conversely, on small installations the allocation is usually generous.
Which disconnection time should I use?
The actual time of the protective device at this fault current, from its characteristic. With current-limiting devices the stress is lower than the formula suggests — then the let-through value from the data sheet applies.
Does this apply to a PEN conductor?
No. A PEN conductor also carries the operating current and is subject to its own minimum sizes. This calculation covers the protective conductor alone.
Calculating is the easy part.
A formula gives you a number. Designing a plant also demands installation method, grouping, discrimination, the standards in force and a look at the installed base. That is what we take on.
More tools
- 01Cable cross-section
- 02Voltage drop
- 03Cable resistance
- 04Cable losses
- 05Maximum cable length
- 06Current-carrying capacity
- 07Parallel cables
- 08Conductor temperature
- 09Cable capacitance
- 10Short-circuit current
- 11Cable impedance
- 12Network impedance
- 13Short-circuit current at the far end
- 14Thermal short-circuit withstand
- 15Length and disconnection
- 16Motor current
- 17Torque
- 18Starting current
- 19Star-delta starting
- 20Soft starting
- 21Motor efficiency
- 22Speed control instead of throttling
- 23Speed and slip
- 24Setting the motor protection
- 25Single-phase motor
- 26Motor feeder
- 27Required motor rating
- 28PFD and SIL
- 29PFH and SIL
- 31Earth rod
- 32Touch voltage
- 33Residual current protection
- 34Check discrimination
- 35Connecting a surge arrester
- 36Enclosure cooling
- 37Reference designation
- 38Reactive power compensation
Contact
Tell us what it is about.
A phone call or three lines is enough. From the very start you talk to the people who will later work on your project, not to a distribution list.
Direct
- Phone+49 (0) 5247 4070-66
- Emailinfo@fisekon.com
- AvailabilityMon – Fri, 8:00 – 17:00 CET
Locations
33428 Marienfeld (Harsewinkel)Gütersloh officeWagenfeldstr. 2
33332 Gütersloh
Or write to us
We usually reply within one working day.
