15 — Calculators
Greatest cable length for the disconnection condition
Voltage drop limits cable length — but often it is not the first limit. As length grows the fault current at the far end falls, and at some point it is no longer enough to operate the device. This calculation says where that limit lies.
Result
- Greatest permissible cable length
- —m
- Greatest permissible loop impedance
- —Ω
- Available for the cableWhat remains after deducting the upstream impedance.
- —Ω
- Length at the next size upWith the protective conductor growing along.
- —m
Please fill all fields with valid numbers.
- Opens the print dialog. Choose “Save as PDF” as the destination.
- Opens your email program with the values from this calculation. Nothing is sent to us until you send it yourself.
A guide, not a design to standard. We give no warranty for the correctness of the results, the applicable standards and case-by-case verification govern.
Worked example
The default case the calculator starts with, worked through once. Change the values above and it recalculates immediately.
Inputs
- System voltage (line to line)
- 400 V
- Voltage factor c
- 0.95
- Operating current of the protective device I_a
- 160 A
- Upstream impedance
- 0.05 Ω
- Line conductor cross-section
- 16 mm²
- Protective conductor cross-section
- 16 mm²
- Conductor material
- Copper (κ = 56 m/Ω·mm²)
- Conductor temperature under fault
- 80 °C
Result
- Greatest permissible cable length
- 479 m
- Greatest permissible loop impedance
- 1.37 Ω
- Available for the cable
- 1.32 Ω
- Length at the next size up
- 748 m
Formula
- Z_max = c · U₀ / I_a with U₀ = U / √3
- available for the cable: Z_max − Z_upstream
- Loop resistance per metre: (1/(κ·A_L) + 1/(κ·A_PE)) · [1 + α · (ϑ − 20 °C)]
- L_max = available impedance / resistance per metre
Assumptions and standards
- The calculation uses a heated conductor, because the loop impedance is then highest.
- The inductive component of the cable is not included. At small cross-sections that is acceptable; from about 50 mm² it shortens the permissible length further.
- The upstream impedance is subtracted arithmetically. That is the safe side: the actual loop is geometrically somewhat smaller, so the permissible length is slightly greater than shown.
- Voltage drop is a separate criterion and limits the length independently. The smaller of the two always governs.
Frequently asked
Which limit bites first, voltage drop or the disconnection condition?
It depends on the protective device. At small rated currents with a slow characteristic, voltage drop is usually the tighter limit. At large rated currents or a fast characteristic — that is, a high operating current — it is the disconnection condition. Calculate both and take the smaller value.
Why is the protective conductor included?
Because the fault current returns through it. A protective conductor half the size shortens the permissible length by a third. That is why it is a separate field here rather than an assumption.
What if no value is produced?
Then the upstream impedance alone already exceeds the permissible loop impedance — the device would not operate even with zero metres of cable. In that case the device is wrongly chosen, not the cable too long.
Calculating is the easy part.
A formula gives you a number. Designing a plant also demands installation method, grouping, discrimination, the standards in force and a look at the installed base. That is what we take on.
More tools
- 01Cable cross-section
- 02Voltage drop
- 03Cable resistance
- 04Cable losses
- 05Maximum cable length
- 06Current-carrying capacity
- 07Parallel cables
- 08Conductor temperature
- 09Cable capacitance
- 10Short-circuit current
- 11Cable impedance
- 12Network impedance
- 13Short-circuit current at the far end
- 14Thermal short-circuit withstand
- 16Motor current
- 17Torque
- 18Starting current
- 19Star-delta starting
- 20Soft starting
- 21Motor efficiency
- 22Speed control instead of throttling
- 23Speed and slip
- 24Setting the motor protection
- 25Single-phase motor
- 26Motor feeder
- 27Required motor rating
- 28PFD and SIL
- 29PFH and SIL
- 30Protective conductor size
- 31Earth rod
- 32Touch voltage
- 33Residual current protection
- 34Check discrimination
- 35Connecting a surge arrester
- 36Enclosure cooling
- 37Reference designation
- 38Reactive power compensation
Contact
Tell us what it is about.
A phone call or three lines is enough. From the very start you talk to the people who will later work on your project, not to a distribution list.
Direct
- Phone+49 (0) 5247 4070-66
- Emailinfo@fisekon.com
- AvailabilityMon – Fri, 8:00 – 17:00 CET
Locations
33428 Marienfeld (Harsewinkel)Gütersloh officeWagenfeldstr. 2
33332 Gütersloh
Or write to us
We usually reply within one working day.
