13 — Calculators
Calculate short-circuit current at the end of a cable
At the start of a cable the short-circuit current is large; at the far end it is small. That is exactly where it is decided whether the protective device still operates under fault — and exactly where nobody recalculates, because the cable "has always run like that".
Result
- Short-circuit current line–protective conductorThe smallest fault current — the disconnection condition turns on it.
- —A
- Disconnection condition
- —
- Three-phase short-circuit current
- —A
- Total loop impedance
- —Ω
- Ratio of I_k1 to I_a
- —
Please fill all fields with valid numbers.
- Opens the print dialog. Choose “Save as PDF” as the destination.
- Opens your email program with the values from this calculation. Nothing is sent to us until you send it yourself.
A guide, not a design to standard. We give no warranty for the correctness of the results, the applicable standards and case-by-case verification govern.
Worked example
The default case the calculator starts with, worked through once. Change the values above and it recalculates immediately.
Inputs
- System voltage (line to line)
- 400 V
- Voltage factor c
- 0.95
- Upstream impedance
- 0.05 Ω
- One-way cable length
- 60 m
- Line conductor cross-section
- 16 mm²
- Protective conductor cross-section
- 16 mm²
- Conductor material
- Copper (κ = 56 m/Ω·mm²)
- Conductor temperature under fault
- 80 °C
- Operating current of the protective device I_a
- 160 A
Result
- Short-circuit current line–protective conductor
- 1,018 A
- Disconnection condition
- Met. The fault current is well above the operating current.
- Three-phase short-circuit current
- 1,653 A
- Total loop impedance
- 0.216 Ω
- Ratio of I_k1 to I_a
- 6.36
Formula
- Z_loop = Z_upstream + R_L + R_PE
- I_k1 = c · U₀ / Z_loop with U₀ = U / √3
- I_k3 = c · U / (√3 · Z_three-phase)
- Disconnection condition: I_k1 ≥ I_a
Assumptions and standards
- The upstream impedance is given as a magnitude; its angle is unknown. It is therefore added arithmetically. That slightly overstates the loop and yields the smaller fault current — the safe side.
- The calculation uses a heated conductor, because the loop impedance is then highest and the fault current smallest.
- The operating current is not the rated current. It comes from the device characteristic and belongs to the required disconnection time.
Frequently asked
Why is the rated current of the device not enough?
Because a miniature circuit breaker only trips magnetically at a multiple of its rated current. With a type C characteristic that is around ten times. A 16 A device therefore needs roughly 160 A of fault current to disconnect within the required time — not 16 A.
What does "tight" mean in the assessment?
That the condition is met on paper but without meaningful margin. The inputs are rarely exact: the upstream impedance varies with the state of the network, the conductor temperature with the load. Below 1.25 times the operating current I would measure rather than rely on the calculation.
What if the condition is not met?
Four routes: a larger cross-section, a shorter cable, a device with a lower operating current or a different characteristic — or a residual current device, which disconnects independently of the short-circuit current. Which route is right depends on the installation.
Calculating is the easy part.
A formula gives you a number. Designing a plant also demands installation method, grouping, discrimination, the standards in force and a look at the installed base. That is what we take on.
More tools
- 01Cable cross-section
- 02Voltage drop
- 03Cable resistance
- 04Cable losses
- 05Maximum cable length
- 06Current-carrying capacity
- 07Parallel cables
- 08Conductor temperature
- 09Cable capacitance
- 10Short-circuit current
- 11Cable impedance
- 12Network impedance
- 14Thermal short-circuit withstand
- 15Length and disconnection
- 16Motor current
- 17Torque
- 18Starting current
- 19Star-delta starting
- 20Soft starting
- 21Motor efficiency
- 22Speed control instead of throttling
- 23Speed and slip
- 24Setting the motor protection
- 25Single-phase motor
- 26Motor feeder
- 27Required motor rating
- 28PFD and SIL
- 29PFH and SIL
- 30Protective conductor size
- 31Earth rod
- 32Touch voltage
- 33Residual current protection
- 34Check discrimination
- 35Connecting a surge arrester
- 36Enclosure cooling
- 37Reference designation
- 38Reactive power compensation
Contact
Tell us what it is about.
A phone call or three lines is enough. From the very start you talk to the people who will later work on your project, not to a distribution list.
Direct
- Phone+49 (0) 5247 4070-66
- Emailinfo@fisekon.com
- AvailabilityMon – Fri, 8:00 – 17:00 CET
Locations
33428 Marienfeld (Harsewinkel)Gütersloh officeWagenfeldstr. 2
33332 Gütersloh
Or write to us
We usually reply within one working day.
