34 — Calculators
Check discrimination between two protective devices
Discriminating means that under fault only the device in front disconnects, not half the installation. That has to be checked separately in two ranges, because they behave differently — in the overload range the current ratio decides, in the short-circuit range the combination of devices.
Result
- Discrimination in the short-circuit range
- —
- Discrimination in the overload range
- —
- Current ratio present
- —
- Margin to the selectivity limit currentNegative means the short-circuit current lies above it.
- —kA
Please fill all fields with valid numbers.
- Opens the print dialog. Choose “Save as PDF” as the destination.
- Opens your email program with the values from this calculation. Nothing is sent to us until you send it yourself.
A guide, not a design to standard. We give no warranty for the correctness of the results, the applicable standards and case-by-case verification govern.
Worked example
The default case the calculator starts with, worked through once. Change the values above and it recalculates immediately.
Inputs
- Rated current of the upstream device
- 160 A
- Rated current of the downstream device
- 63 A
- Required current ratio in the overload range
- 1.6
- Selectivity limit current from the manufacturer table
- 3 kA
- Short-circuit current at the downstream device
- 4.2 kA
Result
- Discrimination in the short-circuit range
- Not achieved.
- Discrimination in the overload range
- Achieved.
- Current ratio present
- 2.54
- Margin to the selectivity limit current
- -1.2 kA
Formula
- Overload: I_n(upstream) / I_n(downstream) ≥ factor
- Short circuit: I_k at the downstream device ≤ selectivity limit current
Assumptions and standards
- The selectivity limit current follows from no formula. It arises from the interaction of both characteristics and their limiting behaviour and is given in the manufacturer coordination table. We do not reproduce those tables — they apply per device pair and series.
- The required current ratio in the overload range is an empirical value for devices of the same kind. For mixed types — fuse against circuit breaker — it does not simply hold.
- Discrimination between two devices is checked. In a chain with several levels, every pair has to be checked separately.
Frequently asked
Why two separate ranges?
Because two different releases are at work. In the overload range the thermal release responds slowly, and a sufficient gap between rated currents suffices. In the short-circuit range both devices release magnetically within milliseconds — there no current gap helps, only that the downstream device limits the current before the upstream one responds.
Why is the limit current not built into the calculator?
Because it is not a calculable value but a measured one per device combination. Manufacturers determine it in the test lab and publish it in coordination tables. A reproduced table would at best be redundant and at worst wrong.
What if there is no discrimination in the short-circuit range?
Either choose a different device pair whose limit current lies above the short-circuit current, or reduce the short-circuit current — longer feeder, smaller cross-section, upstream impedance. Or deliberately accept the loss where disconnecting a larger area is tolerable.
Calculating is the easy part.
A formula gives you a number. Designing a plant also demands installation method, grouping, discrimination, the standards in force and a look at the installed base. That is what we take on.
More tools
- 01Cable cross-section
- 02Voltage drop
- 03Cable resistance
- 04Cable losses
- 05Maximum cable length
- 06Current-carrying capacity
- 07Parallel cables
- 08Conductor temperature
- 09Cable capacitance
- 10Short-circuit current
- 11Cable impedance
- 12Network impedance
- 13Short-circuit current at the far end
- 14Thermal short-circuit withstand
- 15Length and disconnection
- 16Motor current
- 17Torque
- 18Starting current
- 19Star-delta starting
- 20Soft starting
- 21Motor efficiency
- 22Speed control instead of throttling
- 23Speed and slip
- 24Setting the motor protection
- 25Single-phase motor
- 26Motor feeder
- 27Required motor rating
- 28PFD and SIL
- 29PFH and SIL
- 30Protective conductor size
- 31Earth rod
- 32Touch voltage
- 33Residual current protection
- 35Connecting a surge arrester
- 36Enclosure cooling
- 37Reference designation
- 38Reactive power compensation
Contact
Tell us what it is about.
A phone call or three lines is enough. From the very start you talk to the people who will later work on your project, not to a distribution list.
Direct
- Phone+49 (0) 5247 4070-66
- Emailinfo@fisekon.com
- AvailabilityMon – Fri, 8:00 – 17:00 CET
Locations
33428 Marienfeld (Harsewinkel)Gütersloh officeWagenfeldstr. 2
33332 Gütersloh
Or write to us
We usually reply within one working day.
